Jablotron JA-111ST Bus combined smoke and temperature detector

Out of stock. Archived Product.

The JA-111ST is a component of the JABLOTRON JA-100 alarm system. It is used to detect fire hazards in the interior of residential or commercial buildings. The product is not designed to be installed in industrial premises. The detector is powered via the control panel digital bus (EN 54-7; EN 54-5). When the detector is used with inserted batteries (3x 1.5V AA) from which it can be powered, it can continue operating as a stand-alone detector when the 12 V power supply is disconnected (EN 14604).

Jablotron JA-111ST Bus combined smoke and temperature detector

Jablotron JA-111ST Bus combined smoke and temperature detector


The detector indicates fire hazard using the built-in LED indicator and acoustic signalling.


Jablotron JA-111ST Bus combined smoke and temperature detector

Jablotron JA-111ST Bus combined smoke and temperature detector


The JA-111ST consists of two independent detectors – an optical smoke detector and a heat detector. The optical smoke detector works on the principle of scattered light. It is very sensitive to large dust particles which are present in dense smoke. It is less sensitive to smaller particles generated by the combustion of liquids such as alcohol. That is why the fire detector also contains a built-in heat detector which has a slower reaction but is much better at detecting fire which generates only a small amount of smoke.

The detectors must not be installed directly by ventilation or air conditioning vents. In the case of air being supplied through a perforated ceiling, each detector must be placed so that no perforation hole occurs within 0.6m of the detector.


Specification
Download